it seems that i forgot the very basic of PI tag attribute - Location1.
Thanks to Stephen from Osisoft who highlighted this issue, from the ICU the ID is set to 5 - therefore any tag getting the data from this PI-PE interface must have Location1 = 5.
A knowledge sharing portal from an ordinary human serving his exciting professional life as a Instrument & Control System Engineer.. Life is all about sharing.. All knowledge comes from Allah the almighty.. Subhanallah..
28 August 2009
Mark V - IO_CFG.LST Change Detection for SOE
in IO_CFG.LST u can check under TCDA card definition (just search for TCDA) u can see that the Chg Det is set to 1 (which is ENABLED).
Having this turned on for that particular card / contact input will enable Change Detection for SOE purposes.
On the other hand, u can check CONFIG.DAT to see whether SOE will be printed or not. Having SOE enabled does not necessarily required it to be printed (at least this is the case at PPSB Power Plant).
Having this turned on for that particular card / contact input will enable Change Detection for SOE purposes.
On the other hand, u can check CONFIG.DAT to see whether SOE will be printed or not. Having SOE enabled does not necessarily required it to be printed (at least this is the case at PPSB Power Plant).
27 August 2009
Creating a calculated PI tag using PI Performance Equation
So now, DOE requested for a reading from our CEMS system. They wanted a 30 mins average tag for NOx and CO reading.
PI Performance Equation can be used to provide average reading for CEMS_NOX and store it using new tag name.
In this case, we use a new tag called CEMS_NOX_2.
the most important part is to correctly specify the calculation formula under ExDesc attribute.
this is what i used.
TagAvg('CEMS_NOX','*-30m','*')
the format is actually...
TagAvg(tagname,start time, end time)
using PI Processbook, u can verify the tag's attribute..

PI Performance Equation can be used to provide average reading for CEMS_NOX and store it using new tag name.
In this case, we use a new tag called CEMS_NOX_2.
the most important part is to correctly specify the calculation formula under ExDesc attribute.
this is what i used.
TagAvg('CEMS_NOX','*-30m','*')
the format is actually...
TagAvg(tagname,start time, end time)
using PI Processbook, u can verify the tag's attribute..

Subscribe to: