A knowledge sharing portal from an ordinary human serving his exciting professional life as a Instrument & Control System Engineer.. Life is all about sharing.. All knowledge comes from Allah the almighty.. Subhanallah..
29 December 2021
Sample PI Tag Attributes (Digital Values) for OPC Data Access (DA) Interface Node
Sample PI Tag Attributes (Analog Values) for OPC Data Access (DA) Interface Node
Selected(x) x
Name = TAGNAME_001
ObjectType = PIPoint
NewName =
Description = GT1 TFX ACETYLENE
digitalset =
displaydigits = -5
engunits = ppm
exdesc =
future = 0
pointsource = TFX
pointtype = Float32
ptclassname = classic
sourcetag =
archiving = 1
compressing = 1
compdev = 0
compmax = 28800
compmin = 0
compdevpercent = 0
excdev = 0
excmax = 600
excmin = 0
excdevpercent = 0
scan = 1
shutdown = 1
span = 5000
step = 1
typicalvalue = 7.5
zero = 0
convers = 0
filtercode = 0
instrumenttag = MODBUS_TCP_01.GT1.ANALOG11_ACETYLENE
location1 = 3
location2 = 0
location3 = 1
location4 = 1
location5 = 0
squareroot = 0
srcptid = 0
totalcode = 0
userint1 = 0
userint2 = 0
userreal1 = 0
userreal2 = 0
datasecurity = piadmin: A(r,w) | piadmins: A(r,w) | PIWorld: A(r)
ptsecurity = piadmin: A(r,w) | piadmins: A(r) | PIWorld: A(r)
changedate =
changer =
creationdate =
creator =
pointid =
Sample Attributes for PI Tags "SINUSOID"
After installing fresh PI Server 2018 SP3.. Unlike the old days.. the simulated tag "SINUSOID" is no longer bundled in the installer..
You got to install new interface, configure PI-ICU and create the tag yourselves.. (why la OSIsoft bikin susah2 like this) haiyaaa.... 😑😑😑😑😒😓
Nota Kaki : The interface name is PI Random Data Simulator
// Sample Attributes
Selected(x) = x
Name = SINUSOID
ObjectType = PIPoint
Error =
NewName =
Description = 12 Hour Sine Wave
digitalset =
displaydigits = -5
engunits = TBA
exdesc =
future = 0
pointsource = R
pointtype = Float32
ptclassname = classic
sourcetag =
archiving = 1
compressing = 1
compdev = 2
compmax = 28800
compmin = 0
compdevpercent = 2
excdev = 1
excmax = 600
excmin = 0
excdevpercent = 1
scan = 1
shutdown = 1
span = 100
step = 0
typicalvalue = 50
zero = 0
convers = 1
filtercode = 0
instrumenttag =
location1 = 0
location2 = 2
location3 = 0
location4 = 1
location5 = 0
squareroot = 0
srcptid = 0
totalcode = 0
userint1 = 0
userint2 = 0
userreal1 = 0
userreal2 = 0
datasecurity = piadmin: A(r,w) | piadmins: A(r,w) | PIWorld: A(r)
ptsecurity = piadmin: A(r,w) | piadmins: A(r,w) | PIWorld: A(r)
changedate = 2021-10-08 15:40:29
changer =
creationdate = 2021-09-17 08:20:20
creator = piadmin
pointid = 4
recno = 4
02 December 2021
Enabling OPC UA Server using Crimson 3.1 for Red Lion Controls Edge Control
This is OPC Expert software. My favorite OPC testing tools. |
Port 4840 is default for OPC UA. But i learnt that the settings for "browsing" is crucial for 3rd party apps to connect and browse the tags freely. |